TECHNICAL DATA
| Nominal Cross Sectional Area |
Number/ Nominal Dia of Wires (Max.) |
Number/ Nominal Dia of Wires (Max.) |
Thickness of Insulation |
Approx Overall Dia |
D.C. Resistance Max. at 20° C |
Max. Current Carrying Capacity |
|---|---|---|---|---|---|---|
| 2 Core | 2 Core | |||||
| Sq. mm | Number/mm | mm | mm | mm | Ω / Km | Amps |
| 2C X 0.5 | 16/0.2 | 0.6 | 0.90 | 6.00 | 39 | 4 |
| 2C X 0.75 | 24/0.2 | 0.6 | 0.90 | 6.30 | 26 | 7 |
| 2C X 1.0* | 14/0.3 | 0.6 | 0.90 | 7.10 | 18.10 | 12 |
| 2C X 1.5* | 22/0.3 | 0.6 | 0.90 | 7.70 | 12.10 | 16 |
| 2C X 2.5* | 36/0.3 | 0.7 | 1.00 | 8.80 | 7.41 | 22 |
| 2C X 4 | 56/0.3 | 0.8 | 1.00 | 10.20 | 4.95 | 29 |
| 2C X 6 | 84/0.30 | 0.8 | 1.10 | 12.50 | 3.30 | 37 |
| 2C X 10 | 140/0.3 | 1.0 | 1.30 | 16.40 | 1.91 | 40 |
| 2C X 16 | 224/0.3 | 1.0 | 1.40 | 19.40 | 1.21 | 55 |
| 2C X 25 | 354/0.3 | 1.2 | 1.40 | 23.80 | 0.780 | 70 |
| 2C X 35 | 495/0.3 | 1.2 | 1.60 | 27.20 | 0.554 | 90 |
| 2C X 50 | 703/0.3 | 1.4 | 2.00 | 32.00 | 0.386 | 120 |
NOTE:
- THE NUMBER OF WIRES AND DIAMETER MENTIONED IN THE TABLE ARE APPROXIMATE AND NOMINAL, HOWEVER THEY SHALL MEET THE REQUIREMENTS OF CONDUCTOR RESISTANCE AS PERSTANDARDS. IS 8130
- TOLERANCE:- UP TO 4.0 SQ MM +/-0.5 MM. 6.0 SQMM& 10 SQMM+/-1.0 MMAND ABOVE 10 SQ MM+/-1.2 MM
- THE ABOVE DATA IS INDICATIVE AND MAY BE REVISED WITHOUT PRIOR INFORMATION. ZIPCON CABLES WILL NOT BE LIABLE FOR ANY DAMAGES ARISING OUT OF INCORRECTAPPLICATION.