Control Cable
TECHNICAL DATA
Nominal
Cross
Sectional
Area of
Conductor
Number/
Nominal
Dia of
Wires
(Nom)
Thickness
of
Insulation
(Nom.)
Thickness of Sheath (Nom.) Approx Overall Dia D.C.
Resistance
Max. at 20° C
Max.
Current
Carrying
Capacity
6 Core 7 Core 10 Core 12 Core 16 Core 19 Core 24 Core 6 Core 7 Core 10 Core 12 Core 16 Core 19 Core
Sq. mm Number/mm mm mm mm mm mm mm mm mm mm mm mm mm mm Ω/km Amps
0.5 16/0.2* 0.6 0.90 0.90 1.0 1.0 1.1 1.1 1.2 7.60 9.20 12.20 13.30 14.00 16.40 39 4
0.75 24/0.2* 0.6 1.0 1.0 1.1 1.1 1.2 1.2 1.3 9.80 9.80 13.00 14.40 15.10 17.80 26 7
1.0 14/0.3 0.6 1.0 1.0 1.1 1.1 1.2 1.3 1.4 10.50 10.50 14.70 16.40 17.30 20.20 18.10 12
1.5 22/0.3 0.6 1.0 1.0 1.1 1.1 1.2 1.3 1.4 12.40 12.40 16.20 18.00 19.30 22.90 12.10 16
2.5 36/0.3 0.7 1.0 1.0 1.3 1.3 1.4 1.4 1.5 14.20 14.20 19.20 21.50 23.30 27.00 7.41 22
  • THE NUMBER OF WIRES AND DIAMETER MENTIONED IN THE TABLE ARE APPROXIMATE AND NOMINAL, HOWEVER THEY SHALL MEET THE REQUIREMENTS OF CONDUCTOR RESISTANCE AS PERSTANDARDS. IS 8130
  • TOLERANCE:- UP TO 4.0 SQ MM +/-0.5 MM. 6.0 SQMM& 10 SQMM+/-1.0 MMAND ABOVE 10 SQ MM+/-1.2 MM
  •  THE ABOVE DATA IS INDICATIVE AND MAY BE REVISED WITHOUT PRIOR INFORMATION. ZIPCON CABLES WILL NOT BE LIABLE FOR ANY DAMAGES ARISING OUT OF INCORRECTAPPLICATION.